48v inverter output short circuit and output voltage protection instructions

Column:Industry News Time:2021-10-19
When the inverter output feedback does not have a zero-crossing point for 64ms continuously,

(1) Output short-circuit protection of the inverter

When the inverter output feedback does not have a zero-crossing point for 64ms continuously, it is regarded as an output short circuit, the UPS output is turned off, the UPS beeps for a long time and an alarm is displayed on the panel.

(2) Output voltage protection of the inverter

When the inverter output feedback voltage is lower than 140V or higher than 276V for 80ms continuously, it is regarded as output undervoltage or overvoltage for protection, the UPS transfers to bypass mode, the UPS beeps for a long time and an alarm is displayed on the panel.

(3) BUS overvoltage protection of the inverter

When the BUS voltage exceeds 440V for 64ms continuously, it is considered that the BUS is over-voltage and protected, the UPS transfers to the bypass mode, the UPS beeps for a long time and an alarm is displayed on the panel.

(4) Inverter current limiting protection

The protection circuit monitors the output current value. If it exceeds 3.6 times the rated current, the current-limiting protection circuit immediately turns off the PWM and resets the PWM at a 19.2kHz cycle until the output current value is less than 3.6 times the rated current.

(5) Over-temperature protection of the inverter

When the system temperature is too high, the temperature switch trips, making the UPS transfer to bypass mode, the UPS beeps for a long time and an alarm is displayed on the panel (detection time 0.5s).

(6) Load protection of inverter


110%~130%

If the UPS detects that the load exceeds 110% before jumping from the bypass to the inverter, it cannot enter the inverter state. At this time, the UPS beeps once every 0.5s and displays the status on the panel. If the load is detected between 110% and 130% after power-on, the UPS will beep once every 0.5s and display the status on the panel. After 10s, the UPS will switch to bypass mode; after that, if the load is reduced to below 100%, the UPS Restart the soft boot. If the UPS detects that the load is between 110% and 130% in the battery power supply mode, the UPS will beep every 0.5s and display the status on the panel; if the load is not reduced below 100%, the UPS will transfer to bypass after 10s Mode, this state can only be released by pressing the OFF button.


Greater than 130%

If the load is detected to be greater than 130% after power-on, the UPS will beep once every 0.5s, and the status will be displayed on the panel, and the UPS will transfer to the bypass state. After that, if the load is reduced to below 100%, the UPS restarts. If the UPS detects that the load is greater than 130% in the battery power supply mode, the UPS will beep every 0.5s and display the status on the panel; at the same time, the UPS will switch to bypass mode; this status can only be released by pressing the OFF button.


主站蜘蛛池模板: 性色aⅴ闺蜜一区二区三区 性色a v 一区 | 四虎国产在线观看 | 免费v片视频在线观看视频 免费va在线观看 | 家庭教师姐姐 | 一本大道香蕉高清视频在线 | 国产高清在线免费观看 | 青青青青久久久久国产的 | 日韩欧美视频一区二区 | 四虎精品视频 | 成人三级精品视频在线观看 | 四虎影院永久免费 | 国内自拍第五一页 | 91天堂素人精品系列全集亚洲 | 男女www | 久久国产精品二区99 | 亚洲欧美日本另类 | 高清色本在线www | 久久精品国产清高在天天线 | 日本 视频 在线 | 亚洲一区二区三区不卡视频 | 牛牛视频在线 | 麻豆小说 | 久久久久久久久久免免费精品 | 欧美视频在线一区二区三区 | 天天艹逼 | 久久久不卡国产精品一区二区 | 亚洲欧洲一区二区三区在线 | 四虎国产欧美成人影院 | 久久er热视频在这里精品 | 日韩黑丝 | 啦啦啦视频在线视频免费4 啦啦啦视频在线观看影院 啦啦啦社区手机在线视频免费视频 | 性情视频在线高清免费 | 91精品国产人成网站 | 亚洲天堂v| 男女操操操 | 婷婷丁香色综合狠狠色 | 国产欧美成人一区二区三区 | 欧美人体在线 | 色噜噜狠狠色综合久 | www青青草原 | 亚洲欧美二区三区久本道 |